April 02
Long-term operation of air conditioning equipment can easily lead to dust accumulation and component wear, affecting operating efficiency and even causing malfunctions. This article summarizes key points for the maintenance of air conditioning units for operation and maintenance personnel to refer to, standardize operations, and avoid risks.
I. Core Maintenance Outline for Air Conditioning Units
1. Maintenance and upkeep of chiller units:
Check if the three-phase voltage of the power supply is normal at 380V.
Check if the oil heater is working properly when powered on (the oil temperature should be maintained at 25~30℃ when in standby mode).
Check all parts of the machine for leaks or oil seepage.
Check if the temperature control probe is working properly.
Check whether each parameter of the unit is within the standard value during operation.
Check that the loading and unloading solenoid valves and slide valve mechanisms are flexible.
Check if the sound of the unit is normal during normal operation.
Check whether the temperature of the unit is normal during normal operation.
Including main motor, compressor, exhaust temperature, temperature, etc.
Measure the insulation resistance of the main motor and check whether it meets the value specified by the unit.
Check if the seal between the main motor and the compressor is normal.
Check whether the alignment of each safety protection device meets the specified requirements.
Check if the water flow protection switch is functioning properly; if it malfunctions, repair or replace it promptly.
Check the condition of the insulation layer of the evaporator; repair or replace any damaged parts promptly.
Clean scale from the pipes and covers of the evaporator and condenser (water treatment section).
Replace the oil filter element according to usage.
Replace the dryer filter as needed.
Replace the refrigeration oil with new oil depending on its quality.
Lubricate the main motor bearings with grease.
Rust removal and painting of the unit surface.
Calibrate the pressure sensor.
Add or replace the electronically controlled refrigerant.
2. Fan coil unit maintenance
Cleaning: Regularly clean the water tray, air filter, and coil fins to prevent clogging and dust accumulation;
Maintenance: Check the sensitivity of the temperature control switch and the motor's operating status; troubleshoot any abnormal noises or jamming.
3. Cooling tower maintenance
Water supply system: Check the water supply valve and float switch to ensure stable water level;
Water treatment: Regularly add chemicals, test water quality, and prevent scaling and corrosion;
Electric fan: Check operating parameters, add lubricating grease, and clean dust from the blades;
Overall cleaning: Regularly clean the internal packing and water collection tray to ensure heat dissipation.
4. Maintenance and upkeep of air supply and exhaust systems
Cleaning: Clean the filters, louvers, air vents and ducts to remove dust, and clean the fan room;
Maintenance: Check the fan's operating status, add lubricating grease, and ensure the motor insulation is normal.
5. Water pipe system maintenance
Pipeline maintenance: Inspect the pipeline for rust and remove rust and paint as needed;
Parts maintenance: Check valve flexibility and sealing, and calibrate pressure gauges and thermometers;
Pipeline unblocking: Regularly check for blockages and promptly remove debris.
6. Maintenance and upkeep of motors and water pumps
Component maintenance: Check the concentricity of the coupling and the packing seal, and regularly add grease to the bearings;
Safety inspection: The insulation resistance of the motor is tested every quarter to check for potential overheating and leakage.
7. Maintenance and upkeep of the electrical control system
Cleaning: Clean the dust inside the electrical control cabinet to prevent short circuits;
Functional checks: Inspect wiring and terminal connections, and check the accuracy of the automatic control system;
Safety precautions: Check electrical grounding and insulation performance to avoid potential safety hazards.
8. Daily maintenance and upkeep
Check and record the water temperature and water pressure when the main unit is running.
Check and record the operation of the main unit
Refrigerant temperature, evaporator and condenser temperature and pressure.
Check and record the operation of the main unit
And host voltage, current, etc.
Determine if the above data is normal and how to adjust it.
Check the rotating parts for any abnormal vibrations or noises.
Check the pipes and joints for oil or water leaks.
Keep all parts of the host unit clean.
Check if the motor bearing temperature and operating sound are normal.
Check and record the motor voltage and current.
Check the inlet and outlet water temperature and water pressure.
Check the gaskets for damage and leaks.
Check the water supply and pipeline valves to ensure they are functioning properly.
Check the stored water for any floating oil, impurities, or other contaminants.
Check the water level and the float control switch.
Check the operation of the fan motor and the voltage and current conditions.
Pay attention to cleaning the water outlet and filter screen.
Check that all valves and water pipes are in good working order.
Check if the water supply tank and float valve are functioning properly.
The daily inspection record is recorded in the daily inspection record sheet, and is recorded once every 4 hours.
9. Weekly maintenance and upkeep procedures
Check that all safety and operation controllers are functioning properly.
Check if the refrigerant piping system is functioning properly (especially the dryer, expansion valve, solenoid valve, etc.).
Check the refrigeration oil and replenish or replace it if necessary.
Check the safety vent valve.
Check the oil filter and clean or replace it if necessary.
Inspect the bearings and add lubricating oil if necessary.
Check the gasket for leaks.
Check for any looseness between the motor and valve body, and between the valve body and base.
Clean the water tray and the water filter and change the water.
Check the insulation of the motor and wiring.
Combined air conditioning units
Clean the filter screen and replace it if necessary.
Check and adjust the belt tension, and replace it if necessary.
Inspect and clean the windmill and copper pipes.
Check that the current of all motors is normal.
Check all wire ends and connections to ensure they are in good condition.
Remove dust from electrical components and the inside of the box.
Check that the valves, flexible joints, thermometers, pressure gauges and other accessories in the pipeline are in good condition.
Check the filter for blockage and clean it.
Check that all hangers and joints are in good condition and safe.
10. Monthly maintenance and upkeep procedures
Check and pay attention to whether the refrigerant level is insufficient; if it is, it needs to be recharged.
Inspect all safety controllers.
Inspect the piping and exhaust system.
Check the circulating water for contamination and replace it if necessary.
Inspect and replace the oil seals, and add or replace the lubricating oil.
Check the bearings and couplings for damage.
Inspect the water tray, outer casing, and mesh panel; clean or paint if necessary.
Check the water quality, clean and change the water.
Check if the water outlet is working properly; if it is clogged, remove and clean it.
Inspect the piping and purge air.
Clean the windmill and copper pipes.
Check the belt.
Piping and others
Open and close all valves once or twice to prevent blockage.
Check that each electric valve is operating normally.
Table 1. Analysis and Solutions to Common Problems and Faults in Cabinet Fan Coil Units and Combined Air Conditioning Units | |||
part | Problems and faults | Cause Analysis | Solution |
air filter | Increased resistance | Too much dust | Regular cleaning |
Uneven surface temperature | Surface heat exchangers contain air | Open the heat exchanger vent valve to release the vent. | |
Reduced heat exchange capacity | Scale inside the heat exchanger tubes Scale buildup on the surface of the heat exchanger | Remove scale from pipes Cleaning the surface of the heat exchanger | |
water leakage | Interface or Hankou corrosion cracking | repair | |
Air valve not closed or not closed tightly | Close or tighten | ||
Water tray | Overflow | Drain (pipe) blockage | Use methods such as suction, dredging, blowing, and flushing to clear blockages. |
Poor drainage | See the entry below | ||
The drain tray is tilted in the wrong direction. | Adjust the water tray so that the municipal drainage outlet is at its lowest setting. | ||
Poor condensate drainage | The horizontal slope of the external pipeline is too small. | Adjust the slope of the drain pipe to >= 0.8% or shorten the length of the drain pipe to drain water from the nearest available location. | |
The drain outlet (pipe) is partially blocked. | Use methods such as suction, dredging, blowing, and flushing to clear blockages. | ||
The drain outlet of the water receiving pan inside the unit is under negative pressure, and the external drain pipe of the unit does not have a water seal or the water seal height is insufficient. | Install a water seal or increase the water seal height to correspond to the pressure head of the blower. | ||
humidifier | Poor humidification | Humidifier power failure | Overhaul |
Damaged heating element | Repair or replacement | ||
Water supply float valve malfunction | Overhaul | ||
Improper temperature control | Overhaul | ||
Spray chamber | Nozzle blockage | (1) Water filter failure (2) Rust and corrosion inside the metal drain pipes produce slag. | (1) Replacement (2) Enhance water treatment and remove nozzles for cleaning. |
Nozzle cracking | (1) The nozzle has quality problems (such as insufficient material strength, cracks left during manufacturing, etc.). (2) Uneven stress during installation (3) The water pressure of the sprayer is too high | (1) Replacement (2) Replacement (3) Adjust the water pressure to a suitable value. | |
Water-blocking deformation | Insufficient material strength Uneven airflow distribution | (1) Replace (2) Investigate the cause and improve | |
Scale buildup on nozzles or baffles | Poor water quality | Strengthen descaling treatment Remove the nozzle or baffle and clean it with a descaling agent. | |
unit | Condensation on the outer shell | Damage to insulation material | repair |
Damaged casing causing air leakage | repair | ||
Table 2 Key Points for Inspection and Maintenance of Unitary Air Conditioners | ||||
Systems and components | Inspection and maintenance points | |||
daily | Monthly | year | ||
overall | (1) Are the current and voltage normal? (2) Is there any air leakage or condensation in the machine body? (3) Is the indoor unit clean? | Are all fasteners loose? Are there any loose insulation or sound-absorbing materials? | (1) Whether the outer casing of the machine is corroded (2) Whether the exterior of the machine is thoroughly cleaned | |
Refrigeration system | compressor | Are the intake and exhaust pressures normal? Is the noise too loud? | Is the casing temperature too high? | |
Evaporator | Whether condensation occurs | Is there dust accumulation? | ||
Water-cooled condenser | Are the inlet and outlet temperatures of the cooling water normal? Is the cooling water temperature normal? | Have you removed the scale from the pipes? | ||
Expansion valve, dryer filter | Are there condensations or frosts at the inlet and outlet? Is the connection status of the temperature sensor normal? Is the filter clogged? | |||
Refrigeration pipes | Is there a leak? Are the connection parts loose? Are there cracks in the welded area? Is the insulation layer damaged? | |||
air system | Air outlet of direct-blowing model | Are the louvers damaged? Can the louvers swing as controlled? Does the louver produce noise when it oscillates? | ||
Air valves for duct-type units | Does the set position change ? Is there any noise emitted? | |||
Flexible joints for pipeline-type machines | Is it damaged and leaking air? | |||
Filter | Is the filter clean? | |||
Fan | See subsequent tables | |||
Transmission device | See subsequent tables | |||
Drainage system | Water tray | Are there any dirt or water accumulation? Is there any water overflowing? | ||
Drainage tray | Is the drainage unobstructed? | Are the drain pipes old or damaged? | ||
PLC (Power Control System) | Operation switch | Is the contact intact? Is the operation smooth? | ||
indicator lights | Does it indicate normal? | |||
Relay protector | (1) Whether the contact is intact (2) Whether the movements are agile | |||
controller | Are the settings of the high and low voltage controllers appropriate? Are the set values and actions of the temperature controller consistent? | Are the high and low voltage controllers operating normally? | ||
Cooling water system | Valves, flexible joints | Are the valves and flexible joints on the water pipes functioning properly? | ||
Cooling tower | See subsequent tables | |||
water pump | See subsequent tables | |||
water quality | See subsequent tables | |||
Air-cooled outdoor unit | Condenser | (1) Is the surface clean? (2) Is the heat dissipation airflow good? | ||
Fan | See subsequent tables | |||
Heating system | Four-way directional valve | Can it perform a reversing function? | ||
electric heater | Is the heating wire damaged? | Is the insulation good? | ||
hot water or steam heater | Is the outside of the pipe clean? | Is there scale buildup inside the pipe? | ||
Indoor and outdoor unit connection pipes for air-cooled models | Are the insulation sleeves damaged? Are the straps loose? | |||
Table 3. Analysis and Solutions to Common Problems and Faults in Unitary Air Conditioners | ||||||
Problem or malfunction | Cause Analysis | Solution | ||||
The fan is not running or is not blowing air. | power failure Fuse blows Phase loss Poor contact of contactor contacts or burnt-out coil Motor-related faults Fan reverse | (1) Investigate the cause and wait for a reply. (2) Investigate the cause and replace the fuse. (3) Investigate the cause and make up for it. (4) Repair or replacement (5) Refer to the motor fault table. (6) Change the position of any two wires of the motor. | ||||
The fan can run, but the compressor cannot start. | Temperature setting too high Poor contact or intermediate relay connection or burnt-out coil Thermostat malfunction Motor burnout or inter-turn short circuit Overcurrent protector tripped High and low voltage protectors activated | Lower it to an appropriate value Repair or replacement Repair or replacement Repair or replacement Investigate the cause and eliminate the overcurrent fault. Investigate the cause and eliminate the overpressure fault. | ||||
Insufficient cooling capacity | (1) Temperature setting is too high | (1) Lower | ||||
(2) Insufficient air supply | The fan speed setting is too low. Too much dust accumulated in the fresh air filter Evaporator fin oxidation or inter-fin blockage Fan failure Inappropriate fan capacity | improve clean Clean or replace the evaporator See the fan fault table Replace with a suitable fan | ||||
(3) Evaporator surface freezing | Close the expansion valve | |||||
(4) Insufficient refrigerant | Leak detection and sealing, and adding sufficient refrigerant. | |||||
(5) Insufficient opening of the expansion valve | Open to the appropriate position | |||||
(6) Expansion valve blockage | Disassembly and cleaning | |||||
(7) Clogged dryer filter | replace | |||||
(8) Compressor malfunction | Repair or replacement | |||||
(9) The unit capacity is too small | Replace with a larger one or add a new one | |||||
(10) There is air in the refrigeration system. | After removing or re-vacuuming, refill with refrigerant. | |||||
(11) The condensation temperature is too high | Water cooling system | The cooling water volume is too small. | Investigate whether the water pump is faulty or the valve is not fully open. | |||
The inlet water temperature is too high | Investigate whether the cooling tower is malfunctioning or has insufficient cooling capacity. | |||||
Poor heat exchange in condenser | Remove scale from the condenser | |||||
Outdoor wet bulb temperature too high | There is no solution yet. | |||||
air-cooled system | Too much dust on the condenser surface | clean | ||||
Fan failure | See the fan fault table | |||||
Poor ventilation or airflow short circuit | Improve or modify | |||||
There is a heat source nearby. | Remove the heat source or relocate the air-cooling unit. | |||||
outdoor temperature too high | There is no solution yet. | |||||
Excessive operating noise or vibration | A fastener has become loose or fallen off. Fan bearings lacking oil or damaged Loose or deformed fan impeller rubbing against casing Compressor liquid slugging Compressor parts damaged | Tighten or repair Refueling or replacing repair Close the expansion valve slightly or release some refrigerant. Repair or replacement | ||||
The compressor suddenly stopped during the refrigeration process | (1) Low-voltage protector activated | 1) Refrigerant is low 2) Expansion valve is blocked 3) Clogged dryer filter 4) Refrigerant piping throttling 5) Clogged air filter | 1) Detect and seal leaks, and add sufficient refrigerant. 2) Disassembly and cleaning 3) Replacement 4) Identify and repair the cause of the throttling. 5) Clean. | |||
(2) High voltage protector activated | 1) Water-cooled condenser | Insufficient cooling water volume causes the temperature difference between the inlet and outlet water to exceed 8~10°C. Scale buildup or blockage in the condenser The inlet water temperature is too high, exceeding 33°C. | Investigate whether the water pump is faulty or the cooling tower is not returning enough water. Remove scale from the condenser Determine if the problem is caused by a cooling tower malfunction (excluding cases where the outdoor wet-bulb temperature is too high). | |||
2) Air-cooled condenser | Too much dust on the condenser surface The fan does not turn or reverses. Poor ventilation or airflow short circuit The intake air temperature is too high, exceeding 43°C. | clean Investigate the cause and repair or replace the wiring. Improve or change the installation location Investigate the cause and improve | ||||
3) There is air in the refrigeration system. 4) Too much refrigerant charged 5) Inhalation pressure is too high | 3) After removing or re-vacuuming, replenish the refrigerant. 4) Release a portion 5) Analyze the reasons and reduce [the impact]. | |||||
(3) The hydraulic protector is activated. | 1) Excessive refrigerant dissolved in the oil 2) Clogged oil suction filter 3) Insufficient oil level 4) Oil pump failure | 1) Turn on the oil heater 2) Disassemble and clean 3) Investigate the cause of low oil levels, resolve the issue, and add oil at the appropriate flow rate. 4) Perform maintenance. | ||||
(4) Compressor mechanical failure | (4) Repair or replacement | |||||
Indoor unit leaking water | (1) The drain outlet of the water receiving tray and the drain pipe interface are not tight. | (1) The connection is tight and secure. | ||||
(2) Leaking water in the drip tray | 1) Clogged drain outlet (pipe) of water collection tray 2) Poor drainage from the drip tray 3) The machine is under negative pressure during operation and cannot discharge water. | 1) Use methods such as suction, blowing, and flushing to unclog the blockage. 2) Increase the slope and diameter of the drainage pipes. 3) Install a water seal on the external drain pipe or increase the height difference of the gravity drainage. | ||||
Heat pump air conditioners can cool normally, but cannot heat. | Thermostat malfunction The hot/cold switch is malfunctioning. Electromagnetic directional valve malfunction Incorrect connection of electrical control circuit | Repair or replacement Repair or replacement Repair or replacement correct | ||||
Table 4. Analysis and Solutions to Common Problems and Faults in Duct Systems
Problem or malfunction | Cause Analysis | Solution |
Air duct leakage | The flange connection is not tight. Other joints are not tight. | Tighten the bolts or replace the rubber gaskets. Seal with silicone sealant or all-purpose adhesive. |
Insulation layer detaches from duct wall | Adhesive failure Insulation nails detached from the pipe wall | Re-attach firmly Remove the insulation layer, re-attach the insulation nails, and then re-insulate. |
Condensation and dripping water on the surface of the insulation layer | The insulation layer or moisture-proof layer is damaged due to air leakage in the insulated air duct. The insulation layer failed to provide insulation. The adhesive tape at the seam of the insulation layer has come loose. | (1) Referring to the above method, first solve the air leakage problem, and then replace the water-containing insulation layer. (2) Replace damp and water-containing parts (3) Increase the thickness of the insulation layer or replace the insulation material. (4) After replacing the damp or water-containing insulation layer, seal the joints with new adhesive tape. |
The damper is not turning or is not flexible enough. | Foreign object stuck Rust on transmission connecting rod joint | Remove foreign objects Loosen with kerosene and add lubricating oil. |
The air valve cannot be closed tightly | Deformation after installation or use Poor manufacturing quality | Correction Repair or replacement |
The moving blades of the damper cannot be positioned or are easily moved after being positioned. | The control handle cannot be positioned. The active blades are too loose | Improve positioning conditions Tighten properly |
Air vent exposed, dripping water | Supply air temperature is lower than indoor air dew point temperature | Increase the supply air temperature to 2-3°C above the indoor air dew point temperature. Replace the air outlet with one made of a material with lower thermal conductivity (such as wood). |
The airflow from the vent is too strong. | Excessive airflow speed The position of the air outlet guide vanes is not suitable. Inappropriate air outlet design | Open the air vent regulating valve or increase the air vent area. Adjust to the appropriate position replace |
Some air vents have insufficient airflow. | Insufficient opening of branch duct or air outlet valve Excessive pipe resistance Issues related to wind turbines | Increase the pipe cross-section or increase the total pressure of the fan by opening it to a full ten-degree angle. See the fan fault table |
The airflow noise in the duct is too loud | Excessive wind speed | Reduce fan speed or close the air valve. |
The duct walls vibrate and generate noise. | The pipe wall material is too thin | Take measures to strengthen the pipe wall or replace the duct with one of appropriate wall thickness. |
stent exposure, dripping water | The crossbeams of the support frame are in direct contact with the air duct, forming a cold bridge. | Place the support beam outside the duct insulation layer or lay wooden blocks between the support beam and the duct. |
Valve or vent blades vibrate and generate noise. | Excessive wind speed Insufficient stiffness of blade material Loose blades | Reduce wind speed by replacing blades with those that have better rigidity or are made of thicker material. Tighten |
Table 5. Analysis of the causes and solutions to problems related to fresh air usage.
Problems and faults | Cause Analysis | Solution |
Fresh air cannot be supplied. | (1) The area of the fresh air intake is too small. (2) There is no valve in the return air main duct or return air window (door) that can be closed. | (1) Expand or increase the number of fresh air intakes. (2) Add air valves or use other materials for sealing. |
Inaccurate control of fresh air usage | (1) Lack of understanding of the opening characteristics of the fresh air valve (2) The fresh air opening is not fixed. (3) The opening characteristics of the fresh air valve do not meet the adjustment requirements. | (1) Understand the relationship between opening degree and air volume (2) Take fastening measures (3) Replace with a suitable fresh air valve |
The indoor air is not fresh (insufficient fresh air supply). | The fresh air valve opening is too small. The number of people indoors exceeded the designed capacity. | Open to the appropriate degree Control the number of people in the room within the design range |
Table 6. Analysis of the causes and solutions for low room temperature in summer.
Cause Analysis | Solution | |||
Providing too much cooling | (1) Excessive air supply | 1) The opening of the air vent valve is too large. 2) The duct size or air velocity is too large. 3) Improper selection of fan | 1) Close it to a suitable opening degree 2) Adjust the speed of the pipeline valves or the fan. 3) Replace with a fan that has the appropriate airflow. | |
(2) The supply air temperature is too low | 1) The room temperature setting is too low. 2) Chilled water temperature is too low 3) The chilled water flow rate is too high. 4) The new return air ratio is not suitable. 5) Issues related to the refrigeration system of unitary air conditioning units | 1) Adjust to an appropriate value 2) Check for problems with the chiller unit. 3) Close the regulating water valve slightly. 4) When to adjust the ratio 5) See Table 3 | ||
Indoor load less than design value | The design calculations were too conservative, resulting in the selection of oversized air conditioning equipment or an excessive supply of cooling air. Room function change | (1) Close the water valve to reduce the chilled water flow. (2) Adjust the pipe or air outlet valve or fan speed to reduce the air supply volume. (3) Increase the temperature of chilled water supply | ||
Table 7. Analysis of the reasons why room temperature fails to decrease in summer and solutions.
Cause Analysis | Solution | |||
Insufficient cooling capacity | (1) Insufficient air supply | 1) Too much dust accumulated on the surface of the filter or heat exchanger 2) The fan drive belt is loose or slipping. 3) Air leakage in the duct system 4) The opening degree of the air outlet valve is too small. 5) The duct size is too small. 6) Improper fan selection or fan malfunction | 1) Cleaning 2) Tighten or replace the belt 3) Leak sealing 4) How wide should the opening be? 5) Increase wind speed or increase size 6) Replace with a fan of appropriate airflow or troubleshoot the problem. | |
(2) Supply air temperature is too high | 1) Room temperature setting is too high; 2) Chilled water temperature is too high; 3) Chilled water flow rate is too low. 4) Excessive duct temperature rise; 5) Inappropriate fresh air/return air ratio; 6) Problems with the refrigeration system of the unitary air conditioning unit. | 1) Lower it to an appropriate value 2) Check for problems with the water supply to the chiller unit. 3) Open the water valve to the maximum or increase the diameter of the water pipe. 4) Thicken or replace the insulation material 5) When to adjust the ratio 6) See Table 3 for relevant information. | ||
The room was a bit cold. | Room doors and windows not closed or not properly closed Frequent opening of doors | (1) Reduce the number of times the door is opened (2) Close the doors and windows and make them as airtight as possible. | ||
Sunlight streamed into the room | The window has no shade. | Add sunshade devices or replace window glass with sunshade-equipped ones. | ||
Short circuit of supply and return airflow | The distance between the air supply vent and the return air vent is too close (ideally more than 1.5m). Inappropriate air supply direction or air outlet type | Increase the distance between the supply and return air vents Change the air supply direction or change the type of air outlet | ||
Indoor load exceeds design value | Occasionally (e.g., due to excessive number of people) | (1) Lower the freezing temperature, lower the air supply temperature, or increase the air supply volume. | ||
Frequently occurs | (1) Too many devices or personnel have been added indoors. (2) Change of room function | 1) Add air conditioning equipment 2) Modify the original piping to increase cooling capacity. | ||
Table 8. Analysis of the causes and solutions for noise and vibration problems.
Problems and faults | Cause Analysis | Solution |
The operating noise of equipment such as cabinet fan coil units, combined air conditioning units, or unitary air conditioning units affects the air-conditioned room. | Transmitted through the building envelope Entered through the vent Entering through the centralized return air inlet | The computer room was treated for sound absorption, and the computer room doors were treated for sound insulation. Add a silencer to the air supply and return vents, and wrap the ducts with sound insulation material. Replace ordinary louvered centralized return air vents with silencers. |
Vibration from the operation of equipment such as cabinet fan coil units, combined air conditioning units, or unitary air conditioning units can affect the air-conditioned room. | Transmission into the interior through the building envelope | Strengthen the existing vibration damping or isolation devices, or replace them with new and suitable vibration damping or isolation devices. |
Table 9 Common Problems and Fault Analysis and Solutions for Fan Coil Units
Problem or malfunction | Cause Analysis | Solution | |
The fan is running but the air volume is small. | Improper air supply setting Too much dust on the filter Excessive dust accumulation between the coil fins Low voltage Fan reverse | Adjust to the appropriate gear clean clean Investigate the cause Change the phase sequence of the wiring | |
The air blowing out isn't cold (hot) enough. | Improper temperature setting There is air in the coil. Water supply temperature too low or too high Insufficient water supply | Adjust to the appropriate gear Open the coil vent valve to release air. Check cold and heat sources Open the water valve or increase the diameter of the branch pipe | |
Excessive vibration and noise | Poor lubrication or damage to the fan bearings Too much dust or damage to the fan blades Friction between the fan impeller and the casing The air outlet and the external air duct or air supply outlet are not connected by a flexible connection. The coils and drip trays are not flexible connections to the supply, return, and drain pipes. The fan coil unit is telling the current operation Loose connection parts for fixing the fan Loose louvers on air vent | Add lubricant or replace Clean or replace Clean or replace the fan Use soft links Use soft links Adjust to medium or low speed. Tighten Tighten | |
Foreign objects were blown out. | Damaged filter Too much dust in the unit or air duct Rust on the surface of wind turbine blades Coil fin oxidation Damage to insulation material inside the unit or duct | replace clean Replace the fan Replace the coil Repair or replace | |
Unit leaking water | (1) Water overflowing from the drip tray | (1) Clogged drain outlet (pipe) (2) Poor drainage (3) The drainage tray is tilted in the wrong direction. | (1) Use methods such as suction, ventilation, blowing, and flushing to unclog the blockage. (2) Adjust the slope of the drainage pipe to be greater than or equal to 0.8 percent or shorten the length of the drainage pipe to drain the water nearby. (3) Adjust the water receiving tray so that the drain outlet is at its lowest point. |
(2) Leakage and condensation in the pipelines of the unit | (1) The pipe joint is not tight. (2) There are exposed parts of the pipe with condensation on the surface. | (1) Tighten to make the connection tight. (2) Wrap the exposed parts of the pipes with insulation material. | |
(3) Condensation at the bottom of the drip tray | The insulation layer at the bottom of the drip tray is damaged or has detached from the bottom of the tray. | (4) Repair or glue it. | |
(4) The coil vent valve is not closed or not closed tightly. | (4) Close or tighten | ||
Condensation on the unit casing | Damaged or detached insulation material inside the unit Damaged casing causing air leakage | Repair or glue repair | |
Condensate drainage is poor | The horizontal slope of the external pipeline is too small. Drainage outlet (pipe) connection | (1) Adjust the slope of the drainage pipe to be greater than or equal to 0.8 percent or shorten the length of the drainage pipe to drain the water nearby. (2) Use methods such as suction, ventilation, blowing, and flushing to unclog the blockage. | |
Table 10 Analysis and Solutions to Common Problems and Faults in Fans, Motors, and Drive Belts
Problem or malfunction | Cause Analysis | Solution |
bearing temperature rise is too high | Insufficient lubricating oil (grease) Poor quality lubricating oil (grease) The fan shaft and the motor shaft are not concentric bearing damage Two bearings are not concentric | Add enough Clean the bearing and replace with qualified lubricating oil. Two concentric axes replace Find the right |
Excessive noise | Friction between impeller and air inlet or casing Bearing components are worn, and the clearance is too large. Too high speed | See the relevant entries below. Replace or adjust Reduce speed or replace fan |
Excessive vibration | The nuts of the anchor bolts or other connecting bolts are loose. Bearing wear or looseness The fan shaft and the motor shaft are not concentric The connection between the impeller and the shaft is loose. Uneven blade mass or partial blade wear and corrosion Uneven deposits were attached to the leaves. The counterweights on the impeller are of incorrect mass or position. The shafts of the two pulleys of the fan and the motor are not parallel. | Tighten Replace or tighten Adjust concentric Tighten Adjust the balance or replace the blades or impeller. clean Perform balance correction Adjust parallel |
Friction between impeller and air inlet or casing | The bearing is loose in the bearing housing. The impeller center is not at the air inlet center. The connection between the impeller and the shaft is loose. Impeller deformation | Tighten Investigate the cause and make adjustments. Tighten replace |
The air volume is too small. | The impeller rotates in the wrong direction. Insufficient valve opening Belt too loose Insufficient speed Blockage of air inlet or outlet, or ductwork The connection between the impeller and the shaft is loose. Excessive gap between impeller and air inlet The fan is poorly manufactured and does not meet the rated air volume specified by the brand name. | Swap any two wire positions of the motor Open to the maximum and leave the degree Tighten or replace Check voltage and bearings Clear blockages Tighten Adjust to a suitable gap Replace with a suitable fan |
Motor temperature rise is too high | Air volume exceeds rated value There is a problem with the motor or power supply. | Close the air volume regulating valve Find the cause in the motor or power supply. |
problems with drive belts | Belt overfeed (jumping) or overtight Uneven tension when multiple belts are used for transmission The belt is prone to coming off by itself. Belt rubbing against belt protector Belt wear, grease or dirt Belt wears out too quickly | Adjust the motor position to tighten or loosen tension. Replace all Align the corresponding grooves of the two pulleys into a straight line. Tighten the belt or adjust the protective cover. replace Adjust the shafts of the two pulleys of the fan and motor to be parallel. |
Table 11 Analysis and Solutions to Common Water Pump Problems and Faults
Problem or malfunction | Cause Analysis | Solution |
No water comes out of the outlet pipe after startup. | (1) The water in the inlet pipe and pump is seriously insufficient. (2) The impeller rotates in the wrong direction. (3) The inlet and outlet valves are not open. (4) There are foreign objects blocking the water inlet pipe or impeller. | (1) Fill with water (2) Swap the positions of any two wires of the motor (3) Open the valve (4) Remove foreign objects |
The pressure gauge on the outlet pipe shows a reading after startup, but there is no water at the end of the pipeline system. | The speed did not reach the rated value. The resistance of the pipeline system is greater than the rated head of the water pump. | Check if the voltage is too low. Also check if the packing is too tight or if the bearings are not adequately lubricated. Replace with a suitable water pump or increase the pipe diameter or cut off a section of the pipeline. |
After startup, the pointers of the pressure gauge on the outlet pipe and the vacuum gauge on the inlet pipe swing violently. | Air enters the pump through the inlet pipe along with the water flow. | Investigate the source of the air pollution and take measures to prevent it. |
Water initially flowed after startup, but immediately stopped. | A large amount of air is trapped in the water inlet pipe. A large amount of air was inhaled. | Investigate the cause and eliminate air pollution. Check the tightness of the water inlet and pipes, as well as the sealing performance of the shaft seal. |
Water suddenly stopped flowing during operation | Water inlet (port) blocked A large amount of air was inhaled. The impeller was severely damaged. | Clear blockages Check the tightness of the water inlet and pipes, as well as the sealing performance of the shaft seal. Replace impeller |
bearing overheating | Insufficient lubricating oil Lubricating oil aging or poor quality grease Incorrect bearing installation or improper clearance The shafts of the water pump and the motor are not concentric. | Refuel in time Replace with appropriate lubricating oil after cleaning. Adjust or replace Adjust and find |
Excessive leakage from the stuffing box | The packing was not compacted enough Packing wear incorrect packing wrapping method The shaft can bend and wobble. | Tighten the gland or add another layer of filler. replace Rewind correctly Straighten or correct |
Abnormal sound inside the pump | Air is drawn in, causing cavitation. There are solid foreign objects inside the pump. | Investigate the cause and prevent air intake. Disassemble pump and clean |
Pump body vibration | Anchor bolts or all chain bolts and nuts are loose Air is drawn in, causing cavitation. bearing damage Impeller damage Impeller partially blocked The shafts of the water pump and the motor are not concentric. Water pump shaft bent | Tighten Investigate the cause and prevent air intake. replace Repair or replace Disassemble pump and clean Adjust and find Straighten or replace |
The flow rate does not reach the set value | The speed did not reach the set value Insufficient valve opening Water pipes that are too long or too high Piping system with smaller pipe diameter Air intake Foreign objects are blocking the water inlet pipe or impeller. Excessive wear of the sealing ring The impeller is severely worn. Loose impeller fastening screws caused the impeller to slip. | Check voltage, packing, and bearings. Open to the appropriate degree Shorten the water delivery distance or replace with a suitable water pump Increase pipe diameter or replace with a suitable water pump Investigate the cause and prevent air intake. Remove foreign objects Replace the sealing ring Replace impeller Tighten the screw |
The motor consumes too much power. | Too high speed Operating at higher than rated flow and head conditions Packing too tight The water contains mud, sand, or other foreign objects. The shafts of the water pump and the motor are not concentric. Friction between impeller and volute | Check the motor and voltage. Adjust the opening of the outlet pipe valve Relax appropriately Investigate the cause and take cleaning or filtration measures. Adjustment and calibration Investigate the cause and eliminate it. |
Table 12 Analysis and Solutions to Common Cooling Tower Problems and Faults
Problem or malfunction | Cause Analysis | Solution | |
Water temperature too high | Excessive circulating water volume The water outlets in the water distribution pipe (water distribution tank) are blocked, causing uneven water flow. Poor airflow or short circuit Insufficient ventilation The inlet water temperature is too high Air short circuit Partial blockage of the packing material caused uneven water distribution (flow deviation). Outdoor wet bulb temperature too high | Adjust the valve to the appropriate water volume or replace the cooling tower with one of matching capacity. Clear blockages Investigate the cause and improve See solutions for "insufficient ventilation" Checking for problems with the chiller unit Change the air circulation flow to direct current Clear blockages Reduce cooling water volume | |
Insufficient ventilation | (1) The fan speed decreased | 1) Loose drive belt 2) Poor bearing lubrication | (1) 1) Adjust the motor tension or replace the belt. 2) Add oil or replace the bearing |
(2) The angle of the fan blades is not appropriate. (3) Damaged fan blades (4) The packing material is partially blocked. | (2) Adjust the appropriate angle (3) Repair or replacement (4) Clear the blockage | ||
Overflow of water collection tray (trough) | (1) The outlet (filter) of the water collection tray (trough) is blocked. (2) The float valve is malfunctioning and cannot close automatically. (3) The circulating water volume exceeds the rated capacity of the cooling tower. | (1) Clear the blockage (2) Repair (3) Reduce the amount of circulating water or replace the cooling tower with one of matching capacity. | |
The water level in the collection basin (trough) is low. | (1) The float valve opening is too small, resulting in a small water supply. (2) Insufficient water pressure results in a small water supply. (3) There are leaks in the piping system. (4) Excessive water loss during the cooling process (5) The diameter of the water supply pipe is too small. | (1) Open to a suitable opening degree (2) Investigate the cause and increase the pressure or pipe diameter. (3) Locate the leak and seal it. (4) See the solution for "excessive water volume during cooling process". (5) Replacement | |
There is obvious floating phenomenon. | (1) The circulating water volume is too large or too small (2) Excessive ventilation (3) There is a flow deviation phenomenon in the packing. (4) The water distribution device rotates too fast. (5) Improper installation position of the water-blocking sleeve (water baffle) | Adjust the valve to the appropriate water volume or replace the cooling tower with one of matching capacity. Reduce the fan speed, adjust the fan blade angle, or replace the fan with one that provides the appropriate airflow. Investigate the cause and ensure its even distribution. Adjust to the appropriate speed | |
Uneven water distribution | The water outlet of the water distribution pipe (water distribution tank) is blocked. Insufficient circulating water volume The circular water distribution device rotates too slowly. The rotation speed of the circular water distribution tower is unstable and uneven. | Clear blockages Increase the circulating water volume or replace the cooling tower with one of matching capacity. Clear blockages from the water outlet or increase the circulation volume. Air in the duct | |
The packing material and water collection tray (trough) contain dirt or microorganisms. | The environment where the cooling tower is located is too poor. Poor water treatment effect | Shorten the maintenance (cleaning) cycle Research and adjust water treatment solutions to enhance descaling and biodegradation. | |
There are abnormal sounds or vibrations. | The fan speed is too high and the ventilation volume is too large. Fan bearings lacking oil or damaged Fan blades rubbing against other components The nuts on some of the fastening bolts were loose. Loose screws on fan blades Friction between belt and protective cover Gearbox lack of oil or gear set wear Friction between the water-blocking material (water baffle) and the packing | Reduce the fan speed, adjust the fan blade angle, or replace the fan with one that provides the appropriate airflow. Refueling or replacing Investigate the cause and eliminate the possibility. Tighten Tighten Tension the belt and secure the protective cover. Add enough oil or replace the gear set Adjust the baffle and packing | |
The dripping sound is too loud | Packing material deflects water flow Excessive circulating water volume No sound absorber was installed in the water collection tray (trough) | Investigate the cause and ensure its even distribution. Reduce the circulating water volume or replace the cooling tower with one of matching capacity. Install a sound absorber in the water collection tray (trough) | |
| Table 13 Analysis and Solutions to Common Water Valve Problems and Faults | |||
Problem or malfunction | Cause Analysis | Solution |
The valve cannot be closed tightly. | There is debris between the valve core and the valve seat. Wear or damage to the sealing surfaces of the valve core and valve seat | Remove debris Grind the sealing surface or replace the damaged part |
There is leakage between the valve body and the valve cover. | Valve cover not screwed on tightly The gasket between the valve body and the valve cover is too thin or damaged. Uneven tightness of flange connection bolts Valve stem or thread/nut wear | Tighten Thicken or replace Tighten evenly replace |
There is condensation on the valve body surface | Insulated wrapping or incomplete wrapping Insulation layer damage | Insulate or keep the package intact repair |
The stuffing box is leaking. | The packing gland is not tightened or is not properly tightened. Insufficient packing Packing deterioration and failure | Tighten, straighten Refill Replace packing |
Valve stem does not rotate smoothly | Packing too tight Thread wear on valve stem or valve cover Valve stem bent and deformed stuck Scale buildup on valve stems or modified threads Surface corrosion of the valve stem under the packing | Relax appropriately Replace valve Straighten or replace Remove limescale Remove corrosion products |
The check valve spool cannot be opened. | Valve seat and valve core stuck together The valve core shaft is rusted | Remove ditch or rust Remove rust |
The check valve is not closing tightly. | Valve core stuck by debris Valve core damaged | Remove debris Replace valve core |
Table 14 Analysis and Solutions to Common Problems and Faults in Water Piping Systems
Problem or malfunction | Cause Analysis | Solution |
water leakage | The threaded connection was not tightened enough. Insufficient filler for threaded connections The flange connection is not tight. Pipe corrosion perforation | Tighten Apply water-repellent sealant or re-fill and bond the leak. Tighten the bolts or replace the rubber gaskets. Repair welding or replace new pipes |
Insulation layer is damp or dripping | Leaking insulation pipes Damage to insulation or moisture barrier | (1) Refer to the above method to solve the water leakage problem first, and then replace the insulation layer. (2) Replace all damp and water-containing parts. |
There is air in the pipe | Automatic air vent valve not working Insufficient automatic exhaust valve settings Improper setting of automatic air vent valve | Repair or replacement Add at longer bends on the branch ring road It should be installed at the highest point of the water pipeline. |